
FLOW RATE DYNAMICS:
Probable Simultaneous Demand
When sizing pipes for water systems, engineers need to consider the likely consumption of water. But, it’s not required to provide a pipe system that supplies the maximum flow at any one time because all the taps won’t necessarily run at the same time.
When sizing pipes for water systems, engineers need to consider the likely consumption of water. But, it’s not required to provide a pipe system that supplies the maximum flow at any one time because all the taps won’t necessarily run at the same time.
PSD is measured as a flow rate in L/s, m3/s, or GPM
The conversion from loading units or full flow rate to probable simultaneous demand is dependent on what conversion method the user chooses.
H2X offers several probable simultaneous demand conversion methods:
DIN 1988-300:2012-05
AS/NZS 3500.1
Institute of Plumbing Barrie’s Book
IPC 2018
UPC 2018
BS 8558
BS 806
CIPHE

Flow Rate Calculator
H2X TOOLS
Flow rate plays a significant role in determining a water system’s longevity and its day-to-day energy consumption.
THE DIN 1988-300:2012-05 EQUATION
Volume Flow Rate
To manually calculate flow rate and convert the loading units or full flow rate of all the fixtures using the DIN 1988-200:2012-05 equation, you would have to use the following formula:
VS= a ( Σ VR)b - c
Terminology
VS - the peak flow rate
VS - the design flow rate
Where the flow rate is below 0.2l/sec, the full flow rate is used.
Where the full flow rate is higher than 500 l/sec, a flow rate result will not be provided
a, b, c - the constants (as per the table below)

IPC 2018
The following table specifies the sizing methods under the International Plumbing Code for flush tanks:
The following table specifies the sizing methods under the International Plumbing Code for the flushometer:


Dwellings:

INSTITUTE OF PLUMBING:
Barrie’s Book
Loading Units

AS/NZS 3500.1:2018:
Certifying a Cold Water Plumbing Installation
The equation below specifies the method of sizing a typical installation in accordance with AS/NZS 3500.1:2018 for dwellings:
Flow Rate = 0.03n+0.4554√n
The table below specifies the method of sizing a typical installation in accordance with AS/NZS 3500.1:2018 for loading units:

UPC 2018
The following table specifies the sizing methods under the Uniform Plumbing Code for flush tanks:
The following table specifies the sizing methods under the Uniform Plumbing Code for the flushometer:
Flush tanks
Flushometer


BS 8558/ Institute of Plumbing/ CIBSE Guide G
The BS8558 and the CIBSE Guide G are two of the principal flow rate methods employed in the United Kingdom. The loading units take the flow rate into account and the length of time that the outlet will be in use:

BS 806
The BS 806 is one of the principal flow rate methods employed in the United Kingdom for pipe sizing:

MANUAL FLOW RATE CALCULATIONS:
Things To Consider
In some cases, the flow rate of a single fixture will exceed the flow rate provided by the probable simultaneous demand calculation.
For example, a birthing pool may have a flow rate of 1 L/sec but that will get diversified to < 1 L/sec. This means you need to be aware of the pipe sizing, velocity, and pressure loss calculations in that pipe would need to be reviewed with potential modifications made.
Warm water flow rates when using the DIN calculations do not clearly/obviously allow for mixing of hot and cold water to determine the mixed flow rate. Therefore, including when using H2X, the hot water flow rates will be slightly higher than necessary so modifications may need to be made.
Continuous Flow
Continuous flow rates are added to the probable simultaneous demand flow rates to get the total flow rate on a system:
Flow Rate = Probable Simultaneous Demand + Continuous Flow Rates
Cold Water Pipes Supplying a Heated Water Plant
Where a cold water pipe supplies the cold water to fixtures and also the heated water plant that supplies the heated water to the same fixtures, the flow rate will usually take the largest of the two flow rates. However, in some instances, especially in the UK and US, it can be common to combine the loading units together which will allow for a fixtures hot and cold water taps to be used simultaneously.
Volume Flow Rate
Continuous flow rates are added to the probable simultaneous demand flow rates to get the total flow rate on a system:
Flow Rate = Probable Simultaneous Demand + Continuous Flow Rates
Mass Flow Rate
Where a cold water pipe supplies the cold water to fixtures and also the heated water plant that supplies the heated water to the same fixtures, the flow rate will usually take the largest of the two flow rates. However, in some instances, especially in the UK and US, it can be common to combine the loading units together which will allow for a fixtures hot and cold water taps to be used simultaneously.
H2X:
Flow Rate Conversions Made Easy
There are several different methods to convert fixture loading units to probable simultaneous flow rates. Each of the values will assist you in size the piping for plumbing projects.
However, manually completing these calculations can be a lengthy and time-consuming process.

Systems
Choose from cold water, hot water, warm water, or create your own
Parameters
Choose the material, spare capacity, maximum velocity, and minimum pipe size

Parameters
Choose from cold water, hot water, warm water, or create your own


Plant
Add hot water, storage tanks, booster pumps, or create your own
Results
Pipe sizes, peak flow rates, flow velocity, pressure loss, and hot water return
